Technical parameters of withdrawable Thyristor controlled rectifiers:

Parameter name Unit Value
Rectifier power unit design circuit - thyristor-fuse
Connection diagram number (according to EN  50328) - № 9 (12-pulse, bridge)
Rated voltage V 600 750
Rated current A 1000
Auxiliary power network voltage V =110/220*; ~230
Rectifier type of cooling (according to EN 50328) - natural, air (AN)1)
Duty class (according to EN 50328) - IV
Output voltage adjustment range  V 500…700 2) 675…825 2)
Semiconductor devices failure mode (according to EN 50328)  - T mode 3)
Efficiency factor (estimated), minimum % 99
Maximum ambient temperature °С 40
Height above sea level, max, without rated power reduction m 1000
Overall dimensions W x H x D mm 600 x 2200 x 1400
IP class (according to IEC 60529) - IP2X

1) ANAF combined cooling can be applied depending on current load requirements;
2) The parameter is specified by output voltage stabilization requirements;
3) Redundancy is provided by a standby rectifier.