PLUTON presents a new SOTA protection and monitoring system More details
Ukraine |en
Name of parameter U. of m. Value
Structure of rectifier power part - “diode-fuse” “diode-diode”
Rated output voltage V 600, 750, 825
Rated output current А 3000-8000 1200-4000
Duty class (acc. to EN 50328) - VI
Overloads s 1.0 — continuous
1.5 — 7200 s
3.0 — 60 s
Auxiliaries network voltage V =110/220; ~230
Rectification circuit - bridge, 6-,12-pulse
Number of connection circuit (acc. to EN 50328) - 8, 9
Failure mode of semiconductor devices (acc. to EN 50328) - T, F, R modes
Rated network frequency Hz 50
Cooling type (acc. to EN 50328) - natural, air (AN)
Power factor (calculated), min. - 0.95
Efficiency factor (calculated), min. % 98
IP class (acc. to IEC 60529) - IP20