PLUTON presents a new SOTA protection and monitoring system More details
Ukraine |en
Name of parameter U.
of m.
Value
Structure of rectifier power part - “diode-fuse” “diode-diode”
Rated voltage V 600, 750, 825 600, 750, 825 1500, 1650 3000, 3300
Rated current A 4000…8000* 800…4000* 2000…4000* 2000…4000*
Auxiliaries network voltage V =110/220; ~230
Rectification circuit - bridge (6-pulse, 12-pulse)
Number of connection circuit (acc. to EN 50328) - 8, 9, 12
Rectifier cooling type (acc. to
EN 50328)
- natural (AN), forced (AF)
Duty class (acc. to EN 50328) - VI*
Overvoltages -   1.0 — continuous
1.5 — 7200 s
3.0 — 60 s
Failure mode of semiconductor devices (acc. to EN 50328) - T, F, R modes
Maximum ambient temperature °С 40*
Altitude m 1000
IP class (acc. to IEC 60529) - IP20, IP21 IP21 IP21 IP20, IP21, IP43

* other values — upon request