Parameter group | Parameter name | Value |
Network connection | Network voltage Uin | 208…240 V; 380…500 V; 525…690 V; - 10 %...+10 % |
Network frequency | 45…66 Hz | |
Network connection | One per minute or more rarely (normal mode) | |
Motor connection | Output voltage | 0 — Uin |
Continuous output current | IH: maximum ambient temperature +50 °C, overload 1.5 x IH (1 min/10 min) IL: maximum ambient temperature +40 °C, overload 1.1 x IL (1 min/10 min) |
|
Starting moment | Is within 2 s, depends on motor torque | |
Starting current | Is 2 s each 20 s | |
Output frequency | 0…320 Hz (NXS); 7200 Hz (special application) | |
Frequency resolution | 0.01 Hz (NXS); depends on used application (NXP) | |
Control characteristics | Control method | U/f frequency control |
Vector control with open-loop feedback | ||
U/f control with closed-loop feedback | ||
Vector control with closed-loop feedback (only NXP) | ||
Switching frequency (See parameter 2.6.9) |
For drives up to NX_0061 inclusively: 1…16 kHz; Factory setting 10 kHz For drives from NX_0072: 1…10 kHz; Factory setting 3.6 kHz. |
|
Frequency setting: Analogue input Control panel |
Resolution 0,1 % (10-bit), accuracy ±1 % Resolution 0,01 Hz |
|
Field reduction point | 30…320 Hz | |
Acceleration time | 0…3000 s | |
Deceleration time | 0…3000 s | |
Braking moment | DC braking: 30 % * TN (without dynamic breaking unit) | |
Electromagnetic compatibility (default setting) | Interference resistance | Meets all standards requirements |
Interference emission | Electromagnetic compatibility level H: EN 61800-3 (1996)+A11 (2000) (1st environment, restricted distribution); EN 61000-6-4 Electromagnetic compatibility level L: EN 61800-3 (1996)+A11 (2000) (2nd environment) | |
Safety | - | EN 50178 (1997), EN 60204-1 (1996), EN 60950 (2000,3rd edition) (as basic), CE, UL, CUL, FI, GOST R, IEC 61800-5; (For additional information see nameplate) |
Control circuits | Analogue input | 0…+10 V , Ri = 200 k, (–10 V…+10 V joystick control) resolution 0.1%, accuracy ±1% |
Analogue input (current) | 0 (4)…20 mA, Ri = 250 differential | |
Discrete inputs (6) | Positive or negative logic; 18…30 V DC | |
Auxiliary voltage | +24 V , ±15 %, max. 250 mA | |
Reference voltage | +10 V, +3 %, max. load 10 mA | |
Analogue output | 0(4)…20 mA; RL max. 500; Resolution 10 bit; Accuracy ±2 % | |
Discrete outputs | Open-collector transistor, 50 mA/48 V | |
Relay outputs | 2 freely-programmable relay outputs | |
- | Switching capacity: 24 V DC/8 A, 250 V AC/8 A, 125 V DC/0,4 A. min. switchable load: 5 V /10 mA |
|
Protection functions | Overcurrent protection | Tripping limit 4.0*IH |
Overvoltage protection Undervoltage protection |
NX_2: 437 V DC; NX_5: 911 V DC; NX_6: 1200 V DC NX_2: 183 V DC; NX_5: 333 V DC; NX_6: 460 V DC |
|
Earth fault protection | In case of earth fault or in motor cable, only frequency converter protects itself |
|
Supply network phases control | Tripping in case of any supply network phase loss | |
Output network phases control | Tripping in case of any output circuit phase loss | |
Against converter overheating | Available | |
Against motor overload | Available | |
Against motor seizure | Available | |
Against underload operation | Available | |
Against short circuits in +24 V and +10 V circuits | Available | |
Casing class | IР 20, IP 00, IР 21, IP 54 |