Main technical characteristics of AFB arc-free circuit breaker

Parameter name Unit Value
  AFB 25 AFB 40 AFB 40-20
Voltage 
Maximum operating voltage Umax V DC  1000 2000
Insulation voltage UNm V DC  1800 3000
Test impulse voltage UNi kV DC 10 15
Maximum switching overvoltage. Zone B acc. to EN50124.2 (<20 ms)  V DC  <2500 <6000
Current 
Rated service current INe А DC  2500 4000
Duty class acc. to IEC 60146-1-1 - VI
Short-circuit current
Steady-state short-circuit current INss kA 80
Peak of the short-circuit current ȊNss kA 100 115
Maximum breaking current Imax kA 25
Forward current di/dt limit kA/ms 20
Time 
Contacts opening time ms < 1
Total break time ms < 4
Breaking current setting range
- forward breaking current setting range A  400 - 7500 400 - 12000
- reverse breaking current setting range A  400 - 3750 400 - 7500
Weight and size parameters 
Circuit breaker weight kg  215 300 380
Circuit breaker overall dimensions:
Width
Height
Depth (Length)
mm  
475
810
955

475
1050
955

475
1275
955
Additional data
Commutation life switchings 3 х 50 000  4 х 25 000
Protection level  - IP00
Auxiliaries supply voltage V DC 110, 220