Main technical characteristics of PLC-DI-24 input discrete signals module:
Name of parameter | Unit of measurement |
Value |
Number of discrete inputs | - | 24 (one galvanically isolated group) |
Rated input voltage, DC | V | 24 |
Input voltage range, "ON" state (log. 1), DC | V | 10 – 34 |
Input current, "ON" state (log. 1) (upon input voltage 10 V < U < 30 V) | mА | 2.8 – 3.6 per channel |
Input voltage range, "OFF" state (log. 0), DC | V | 0 – 4 |
Minimum input current, "OFF" state (log. 0), max. | mА | 2.0 per channel |
Data response delay at output upon signal switching at input | ms | 0, 1 or 3 (hardware-based) + from 0 up to 5000 (software-based) |
Electrical insulation resistance of galvanically isolated circuits (upon test voltage frequency 50 Hz and testing time 1 min.) | V | 1000 |
Electrical insulation resistance of galvanically independent circuits (at U test = 1000 V DС), min | MОhm | 100 |
Module address setting from 0 up to 15 | - | mechanical switching device |
Interface for communication with control controller | - | RS-485 (Modbus-RTU Slave up to 115200 bps) or CAN (from 50 kHz up to 500 kHz) |
Connection/disconnection of matching impedance of connection line 120 Ohm | - | configured with a parameter |
Module power supply voltage in +24 V DC circuit | V | 12 – 34 |
Module power supply voltage in +5 V DC circuit | V | 4.7 – 5.5 |
Consumption power in +5 V circuit | W | 0.35 |
Environmental conditions | ||
Operation temperature | °C | from -20 up to +45 |
Storage temperature | °C | from -40 up to +60 |
Relative humidity | - | up to 80 % with no condensed water |
Atmospheric pressure | kPa | from 86 up to 106 (645 – 795 mm Hg) |
Operation mode | - | continuous |
Cooling | natural | |
Type of installation | mm | DIN rail, 35 mm |
Protection level DIN EN 60529:2014 | - | IP 20 |