Main technical charcteristics of current relay CR-100
| Name of parameter | Unit of measurement | Value | 
| General | ||
| Relay rated current | A | 100 | 
| Surge currents | kA | 60 (8/20 μs) | 
| 25 (10/350 μs) | ||
| Current sensor type | - | a Hall effect sensor | 
| Possibility of operating threshold setting | - | yes | 
| Possibility of calibration | - | yes | 
| Range of relay operating threshold adjustments | A | -100 … +100 | 
| Discretization of operating threshold switching | A | 10 | 
| Accuracy of adjustment of actuating current | - | ±5 % of rated current | 
| Actuation time, max. | mS | 1 | 
| Indication | - | state of relay digital outputs | 
| Lower and upper limit operating value of ambient air temperature | °С | -10 … +60 | 
| Relative air humidity, %, at a temperature (upper value) | °C | 75, 27 (98, 35)  | 
| Mechanical | ||
| Dimensions (WхHхD) | mm | housing: 52х45х50 busbar: 20х165х5  | 
| Weight | kg | 0.35 | 
| Material of housing | - | polycarbonate (PC) | 
| Busbar cross-section | mm | 20*5 | 
| Busbar connections | - | max. M10 | 
| Material of busbar | - | copper (Cu), aluminium (Al) | 
| Protection level in acc. with GOST 14254, DIN VDE 0470, EN 60529, IEC 60529 | - | IP30 | 
| Type of connection to external circuits | - | connector with screw clamp for cross-sections from  0.2 mm² to 2.5 mm² (from 30 AWG to 12 AWG)  | 
| Tightening moment of connection of external circuts, min-max | N·m | 0.5-0.6 | 
| Type of mounting | - | bolted connection, max. M10…M8 | 
| Power supply | ||
| Rated supply voltage, Urat.sup. | V | 24, DC | 
| Acceptable long-lasting voltage deviation | - | +10%, -15 % | 
| Acceptable pulsation level | - | 10 % Urat.sup. | 
| Power consumption, max: | W | 1 | 
| Digital outputs | ||
| Number of outputs | - | up to 2 | 
| Functional purpose of outputs | - | actuation; state (relay operation monitoring)  | 
| 
 Switching current type  | 
- | constant | 
| Rated voltage | V | 24 | 
| DC switching voltage, max | V | 30 | 
| Long-lasting acceptable current | mA | 100 | 
| Acceptable switching current, max | mA | 200 | 
| Protection against current load exceed | - | implemented | 
| Protection against overloads | - | implemented |